Ron Brown Ron Brown
0 Inscritos en el curso • 0 Curso completadoBiografía
CDCS Exam Fees | CDCS Test Centres
What's more, part of that PDF4Test CDCS dumps now are free: https://drive.google.com/open?id=1wjthM7oys67ioPNM4-SFkQnc_2vz48rC
The candidates can test themselves for the EXIN EPI Certified Data Centre Specialist exam day by attempting the EXIN EPI Certified Data Centre Specialist CDCS practice test on the software. There is preparation material available on the CDCS Practice Exam software by PDF4Test to study for the EXIN CDCS test.
EXIN CDCS Exam Syllabus Topics:
Topic
Details
Topic 1
- Data Centre Life Cycle and Standards: This section of the exam measures the skills of data center professionals and covers the various stages involved in the life cycle of a data center, from planning and design to implementation and decommissioning.
Topic 2
- Data Centre Environmental Considerations and Efficiency: This section evaluates the proficiency of data center professionals in addressing environmental factors and promoting efficiency within data center operations. The target audience, including data center managers and engineers, will be tested on their ability to identify and implement measures that enhance energy efficiency, cooling management, and sustainable practices.
Topic 3
- Designing and Implementing a Data Centre: In this module, the exam assesses the knowledge of Exin data center professionals tasked with the design and implementation of data centers. Candidates will learn the key principles of creating an efficient data center layout, including considerations for scalability, redundancy, and security.
CDCS Test Centres, Valid CDCS Test Duration
You can use CDCS guide materials through a variety of electronic devices. At home, you can use the computer and outside you can also use the phone. Now that more people are using mobile phones to learn our CDCS study materials, you can also choose the one you like. One advantage is that if you use our CDCS Practice Questions for the first time in a network environment, then the next time you use our study materials, there will be no network requirements. You can open the CDCS real exam anytime and anywhere.
EXIN EPI Certified Data Centre Specialist Sample Questions (Q77-Q82):
NEW QUESTION # 77
What is the main disadvantage of using a ToR (Top of Rack) design?
- A. There will be more switches to manage.
- B. A single ToR (Top of Rack) switch is more expensive than an EoR (End of Row) switch.
- C. A ToR (Top of Rack) switch has only optical interfaces.
- D. You need a separate rack to install all your ToR (Top of Rack) switches.
Answer: A
Explanation:
A Top of Rack (ToR) design typically requires more switches because each rack has its own switch to manage network connections, as opposed to End of Row (EoR) or centralized designs, which consolidate switches.
While ToR designs improve cabling efficiency and reduce latency, they also increase the number of switches, thus raising management complexity and potentially increasing capital and operational costs.
Detailed Explanation:
In a ToR setup, each rack's individual switch allows for quick access and streamlined cabling within the rack.
However, this setup means more devices to configure, monitor, and maintain, which can increase administrative overhead and network management complexity.
EPI Data Center Specialist References:
EPI documentation notes that ToR designs can improve performance but also lead to increased management needs due to the higher switch count, making them less ideal in environments where simplified network management is prioritized.
NEW QUESTION # 78
The computer room has high levels of H2S gas contamination. What is the best option to resolve this issue?
- A. Vacuum the whole room using a HEPA/S-Class-based filter.
- B. Clean the room and racks with a damp/wet cloth.
- C. Provide more air changes per hour by adding more fresh air to the computer room.
- D. Install air-scrubbers.
Answer: D
Explanation:
High levels of H2S (hydrogen sulfide) gas contamination in a computer room are best addressed by installing air-scrubbers. Air-scrubbers can effectively filter out contaminants, including corrosive gases like H2S, ensuring clean air circulation and protecting sensitive IT equipment from potential corrosion and damage.
Detailed Explanation:
Air-scrubbers are designed to remove various airborne contaminants and are particularly useful in environments where corrosive gases are present. These systems use filters or chemical reactions to neutralize harmful substances, making them ideal for data centers that need to maintain high air quality for equipment reliability.
EPI Data Center Specialist References:
EPI guidelines suggest air-scrubbing technologies to remove contaminants that pose risks to electronic equipment, maintaining air quality and reducing corrosion risk.
NEW QUESTION # 79
Management has requested a 15-minute battery bank assuming full load on the UPS. The UPS vendor has provided the following specifications of the UPS:
*Rated power: 30 kVA
*Rectifier input voltage: 400 V/3 phase
*Rectifier input power factor: 0.8
*Battery rated voltage: 384 V
*Number of cells: 192
*End of discharge voltage: 308 V
*Inverter output voltage: 400 V/3 phase
*Inverter output power factor: 0.8
What information is missing to perform the battery calculation?
- A. UPS efficiency
- B. Available battery charging current
- C. Inverter efficiency
- D. Load imbalance on the phases
Answer: A
Explanation:
To determine the required capacity of the battery bank for the 15-minute runtime at full load, one must know the total power requirement that the battery bank must supply. The specifications provided include most of the necessary details, such as rated power, input voltage, battery voltage, and discharge voltage. However, one critical piece of information is missing: the UPS efficiency.
Detailed Explanation:
In a data center UPS system, the battery bank is designed to supply power for a set duration when there is an input power failure. The UPS efficiency affects the actual power the UPS can deliver to the load compared to the power it draws from the batteries. The efficiency factor is necessary to accurately calculate the required capacity of the battery bank since it determines how much input power is needed from the batteries to supply the load at full capacity. The formula typically used to determine battery capacity involves factoring in UPS efficiency, as it allows you to understand the losses within the UPS system.
If UPS efficiency is not considered, there would be an inaccurate estimation of the actual power needed from the batteries. For instance, if a UPS has 90% efficiency, only 90% of the power drawn from the batteries reaches the load. Without knowing this efficiency, it is not possible to calculate the battery bank size accurately, as you cannot accurately estimate the losses within the UPS itself.
EPI Data Center Specialist References:
According to EPI Data Center Specialist training, understanding the UPS efficiency is essential for battery sizing. Without it, the calculations could lead to either undersizing or oversizing the battery bank, which affects both reliability and cost-effectiveness of the UPS system. The EPI Data Center Specialist course emphasizes that battery sizing must account for all losses within the UPS system, with efficiency being a primary factor in these calculations.
NEW QUESTION # 80
The air intake of the mission-critical server at the top of the rack is measuring 25 °C/77 °F.
Is this acceptable?
- A. Yes, this is allowed according to the standards and guidelines
- B. As long as it does not exceed the average server room temperature of 38 °C/100 °F
- C. No, the temperature needs to be 20 °C/68 °F
- D. Depends on the ANSI/TIA-942 Rating the data center needs to comply with
Answer: A
Explanation:
An air intake temperature of 25 °C (77 °F) at the top of the rack is acceptable according to data center standards and guidelines, such as those from ASHRAE. This temperature falls within the recommended range for inlet temperatures, which is typically between 18°C (64°F) and 27°C (81°F).
Detailed Explanation:
ASHRAE standards provide guidelines on acceptable temperature ranges for air intake in data centers to balance cooling efficiency and equipment safety. A temperature of 25°C is within the recommended operational range, allowing data centers to optimize energy efficiency while maintaining safe conditions for IT equipment.
EPI Data Center Specialist References:
EPI guidelines align with ASHRAE recommendations for server intake temperatures, confirming that 25°C is within acceptable limits for most mission-critical equipment. This ensures the data center maintains an efficient and reliable environment.
NEW QUESTION # 81
You are allowed to use a calculator for this question. The total power consumption of the ICT equipment in a rack is 6 kW. The equipment is traditional ICT equipment with a Delta-T of approximately 11 °C / 20 °F. Calculate the approximate CFM required to cool the equipment in the rack.
- A. Approximately 1,000 CFM
- B. Approximately 1,500 CFM
- C. Approximately 500 CFM
- D. Approximately 160 CFM
Answer: A
Explanation:
To calculate the cooling airflow requirement for ICT equipment, you can use the formula:
CFM=Power (kW)×3160ΔT(°F) ext{CFM} = rac{ ext{Power (kW)} imes 3160}{Delta T ( ext{°F})}CFM=ΔT(°F)Power (kW)×3160 For equipment consuming 6 kW with a Delta-T of 20°F:
CFM=6×316020=948≈1,000 CFM ext{CFM} = rac{6 imes 3160}{20} = 948 approx 1,000 , ext{CFM}CFM=206×3160=948≈1,000CFM Detailed Explanation:
This formula provides an estimate of the cubic feet per minute (CFM) of air required to cool the equipment based on its power consumption and the temperature difference (Delta-T) between intake and exhaust. The Delta-T represents the cooling effectiveness of the airflow.
EPI Data Center Specialist References:
EPI recommends using this calculation for determining airflow requirements in data centers, ensuring that cooling systems are adequately sized to maintain equipment within safe temperature limits.
NEW QUESTION # 82
......
If you're still learning from the traditional old ways and silently waiting for the test to come, you should be awake and ready to take the exam in a different way. Study our CDCS training materials to write "test data" is the most suitable for your choice, after recent years show that the effect of our CDCS guide dump has become a secret weapon of the examinee through qualification examination, a lot of the users of our CDCS guide dump can get unexpected results in the examination. It can be said that our CDCS study questions are the most powerful in the market at present, not only because our company is leader of other companies, but also because we have loyal users. CDCS training materials are not only the domestic market, but also the international high-end market. We are studying some learning models suitable for high-end users. Our research materials have many advantages.
CDCS Test Centres: https://www.pdf4test.com/CDCS-dump-torrent.html
- 2025 EXIN Newest CDCS: EXIN EPI Certified Data Centre Specialist Exam Fees 🧊 Immediately open ⇛ www.examcollectionpass.com ⇚ and search for ( CDCS ) to obtain a free download ⏸CDCS Online Tests
- Official CDCS Study Guide 🔜 New CDCS Test Book 🧖 New CDCS Test Labs 🌽 Search for 「 CDCS 」 and download it for free immediately on ✔ www.pdfvce.com ️✔️ ✒CDCS Updated Testkings
- 2025 EXIN Newest CDCS: EXIN EPI Certified Data Centre Specialist Exam Fees 🔪 Search on “ www.pass4leader.com ” for ⇛ CDCS ⇚ to obtain exam materials for free download 🖍Latest CDCS Exam Forum
- EXIN CDCS Exam questions are updated recently, and 100% guarantee that you pass the exam successfully! 🥜 Open ➽ www.pdfvce.com 🢪 enter { CDCS } and obtain a free download 👷New CDCS Test Testking
- Trustable EXIN CDCS Exam Fees - CDCS Free Download 😨 The page for free download of ▛ CDCS ▟ on ⏩ www.prep4sures.top ⏪ will open immediately 🕤New CDCS Study Notes
- Valid CDCS Test Blueprint 🥗 CDCS Practice Test Fee 🦃 New CDCS Test Book 🦹 Copy URL ▶ www.pdfvce.com ◀ open and search for ⇛ CDCS ⇚ to download for free 🚝CDCS Authorized Exam Dumps
- EXIN CDCS Exam questions are updated recently, and 100% guarantee that you pass the exam successfully! 🌆 ☀ www.torrentvce.com ️☀️ is best website to obtain 「 CDCS 」 for free download 😅New CDCS Study Notes
- Pass EXIN CDCS Certification with Ease Using Pdfvce Exam Questions 😛 Search for 「 CDCS 」 and download it for free immediately on ⇛ www.pdfvce.com ⇚ 🟥Valid CDCS Test Blueprint
- Latest CDCS Exam Forum 👸 CDCS Practice Test Fee 🎨 CDCS Authorized Exam Dumps 🙅 Download ⏩ CDCS ⏪ for free by simply entering ➠ www.examcollectionpass.com 🠰 website ✔New CDCS Test Labs
- Exam Dumps CDCS Collection 🏗 Authorized CDCS Exam Dumps 🙄 New CDCS Test Book 🔶 Search for ➡ CDCS ️⬅️ and download it for free immediately on ▷ www.pdfvce.com ◁ 👗CDCS Practice Test Fee
- New CDCS Test Book 🤼 Official CDCS Study Guide 🌃 CDCS Test Vce 📸 Copy URL ▛ www.prep4sures.top ▟ open and search for ➤ CDCS ⮘ to download for free 👕Valid CDCS Test Blueprint
- www.stes.tyc.edu.tw, learning.cpdwebdesign.com, bijie.cnrxw.cn, cq.x7cq.vip, abalearningcentre.com.hk, www.stes.tyc.edu.tw, onlineadmissions.nexgensolutionsgroup.com, www.stes.tyc.edu.tw, cq.x7cq.vip, chaceacademy.com, Disposable vapes
2025 Latest PDF4Test CDCS PDF Dumps and CDCS Exam Engine Free Share: https://drive.google.com/open?id=1wjthM7oys67ioPNM4-SFkQnc_2vz48rC